SY-TSS Series
Application Scope
Reactive compensation and harmonic filtering of electric power, petroleum, steel, chemical, metallurgy, wind power, semiconductor manufacturing, water supply and drainage industry.
Technical Features:
There exists serious 3-phase unbalance situation in some power grid, especially in automobile welding workshop. If three phases work together, it will cause overcompensation or undercompensation of the single phase. Single phase split phase compensation adopted is to solve the above issue.
Product Picture
Model Implication
Selection List
SY-TSS-□/□-400型
NO. | Installed Capacity (kvar) | Fundamental Capacity (kvar) | Grading Manner (Coding) | Single-Phase Compensation precision (kvar) | Compensator Num. (set) | Compensation Cabinet Size (L*D*H) | Compensator Capacity (kvar) |
1 | 120 | 96 | Constant capacity 8 grade switching1:1:1:1:1:1:1:1 | 4 | 1 | 1100*1000*2200 | 120 |
2 | 240 | 192 | Constant capacity 8 grade switching1:1:1:1:1:1:1:1 | 8 | 1 | 1200*1000*2200 | 240 |
3 | 360 | 288 | Constant capacity 8 grade switching1:1:1:1:1:1:1:1 | 12 | 1 | 1200*1000*2200 | 360 |
4 | 480 | 384 | Constant capacity 8 grade switching1:1:1:1:1:1:1:1 | 16 | 1 | 1200*1000*2200 | 480 |
5 | 100 | 80 | Coding1:2 | 9 | 1 | 800*1000*2200 | 100 |
6 | 150 | 120 | Coding1:2 | 13 | 1 | 800*1000*2200 | 150 |
7 | 200 | 160 | Coding1:2:4 | 8 | 1 | 900*1000*2200 | 200 |
8 | 250 | 200 | Coding1:2:4 | 10 | 1 | 1000*1000*2200 | 250 |
9 | 300 | 240 | Coding1:2:4 | 11 | 1 | 1000*1000*2200 | 300 |
Description: While grading the capacity, the same capacity cabinet can be extended combining. For example, split compensation cabinet of 240kvar installed capacity, can add one more cabinet with the same capacity to reach 2×240=480kvar.
Note: 1. The voltage grade, capacity and grading manner can be made according to customer requirements.
2. The data in the table are for reference only, we reserve the right to change the data.